Fire dampers installed at a minimal distance from another damper or from an adjacent supporting construction
30/11/2022 - 10:11:14 AM |
442126
According to the European test standard, a fire damper must be installed at a minimum distance of 75 mm from an adjacent wall and 200 mm from another damper, unless the solution was tested at a shorter distance.
According to the European test standard, a fire damper must be installed at a minimum distance of 75 mm from an adjacent wall and 200 mm from another damper, unless the solution was tested at a shorter distance.
The main Rf-t fire dampers have been tested – and may, therefore, be installed – in a vertical or horizontal supporting construction, at a distance below the minimum set by the standard. No less than 90% of the classifications of our fire dampers qualify for this installation method. The minimal distance is reduced to 30 mm for circular dampers and to 50 mm between 2 dampers or between a damper and a vertical wall, and to 25 mm between a damper and a floor/ceiling.

For the Rf-t fire dampers, the solution consists of the following elements: a generic sealing (rigid stone wool panels 150 kg/m³ applied to a depth of 400 mm) at the side with minimal distances and a sealing compliant with existing classifications for the rest of the opening.
Tin liên quan
- Elevate Your Cleanroom Environment: Your One-Stop Solution for Comprehensive Air Handling Units (AHU) Excellence(14/03/2025)
- Customized Cleanroom Air Handling Units (AHU) Solutions(14/03/2025)
- Halton offers fire protection with fire dampers for demanding industrial environments(03/11/2023)
- Rf-Technologies(30/11/2022)
- Smoke Exhaust Systems(13/09/2022)
- MERCOR TECRESA Fire Dampers Passive Fire Protection(09/09/2022)
- DLK Axial Fans(17/11/2021)
- DLK Centrifugal Fans(17/11/2021)
- CAR PARK VENTILATION SYSTEM(17/11/2021)
- DLK APP(17/11/2021)
- CFD SIMULATION(17/11/2021)
- METRO DUBAI Comming soon(17/11/2021)